Plain-language guide

Ontario Fire Code: what your doors actually require

Monthly inspection of fire separation doors, the new egress door duties that arrived on 1 January 2026, who carries the obligation, and what you need to be able to produce. Written from the regulation, with the article numbers so you can check us.

The short version

A door in a fire separation must be inspected monthly — Article 2.2.3.4(4). That is long-standing law, not a 2026 change, and it applies whether or not the door is in regular use. Fire dampers and fire stop flaps are the annual item, under Article 2.2.3.5.

What is new as of 1 January 2026: egress doors are checked monthly to confirm they are operable, and revolving doors, certain sliding doors and electromagnetic locks are tested at intervals not greater than 12 months, with records kept for those tests — Articles 2.7.2.3 and 2.7.2.4.

The obligation falls on the “owner”, which the Code defines as anyone “having control over any portion of the building or property”.

Background

What the Ontario Fire Code is

The Ontario Fire Code is O. Reg. 213/07, made under the Fire Protection and Prevention Act, 1997. It governs how existing buildings must be maintained and operated for fire safety — as distinct from the Ontario Building Code, which governs how buildings are designed and constructed.

That distinction matters. A building can have been built entirely to code and still be in breach of the Fire Code years later, because doors have been modified, closers have failed, labels have been painted over or hold-opens have been fitted.

The Fire Code is enforced locally by municipal fire departments. In practice that means a fire prevention officer from Toronto Fire Services, Hamilton Fire Department, Mississauga Fire or whichever service covers your building. Enforcement culture varies between them.

One definition is worth having in front of you, because it sets what an inspection actually is. The Code defines inspection as a “physical examination to determine that the device or system will apparently perform in accordance with its intended function.” Somebody has to go and look at the door.

Every door duty in the Code

There are seven. This is the complete set — no other provision anywhere in the Fire Code sets a frequency for a door.

  • Article 2.2.3.4(4) — a door in a fire separation is inspected monthly. Long-standing.
  • Article 2.2.3.4(1) and (2) — a door in a fire separation is kept closed when not in use, and checked as frequently as necessary to confirm it stays closed. Long-standing.
  • Article 2.2.3.4(5) — the door opening and the area around it are kept clear of anything that would obstruct or interfere with the free operation of the door. Long-standing.
  • Article 2.2.3.5 — fire dampers and fire stop flaps are inspected annually, or on an approved schedule. Long-standing.
  • Article 2.7.2.3(1) — every door forming part of a means of egress is checked at intervals not greater than one month to confirm it is operable. New on 1 January 2026.
  • Article 2.7.2.3(2), (3) and (4) — revolving door safety features, sliding doors required to swing on their vertical axes in the direction of egress, and electromagnetic locks are each tested at intervals not greater than 12 months. New on 1 January 2026.
  • Article 2.7.2.4 — records of those three 12-month tests are made and retained. New on 1 January 2026.

Note the verbs. The Code treats checking, inspection and testing as three different things, and the distinction decides what has to be written down. Doors in fire separations are inspected. Egress doors are checked. Mag locks, revolving doors and those sliding doors are tested — and tests are what the Code requires records of.

What actually changed on 1 January 2026

O. Reg. 87/25 amended the Fire Code, with sections 1 to 67 in force from 1 January 2026. For doors, the substance is section 18 of the amendment, which inserted Articles 2.7.2.3 and 2.7.2.4 — the egress door, revolving door, sliding door and electromagnetic lock duties listed above.

Sections 10 and 11 also struck the words “in fire separations” from Articles 2.2.3.2(1) and 2.2.3.3. Those are the duties to keep closures maintained and operable, and unobstructed and not wedged open. Removing that qualifier widens both beyond fire separations to closures generally. Section 12 added Subsection 2.2.4, on damaged or removed encapsulation materials in mass timber construction.

Electromagnetic locks

This is the change most likely to catch a secured building, because almost every commercial building in the GTA has mag locks and almost nobody is testing them on a 12-month cycle with a record.

One point is widely misstated, so it is worth being precise. The Fire Code permits an electromagnetic locking device on an access to exit or an exit door only where it is approved or complies with the Building Code — Article 2.7.2.2(2). The release behaviour is set by that approval, not by the Fire Code. What the Fire Code requires of you is that the lock be tested on a 12-month cycle and the result recorded. A lock that no longer does what it was approved to do is both a hazard and a failed test.

That same Article prohibits electromagnetic locking devices outright in two places: on a door in an elementary or secondary school, and on an egress or exit door serving a high-hazard industrial occupancy.

What did not change: monthly inspection

A great deal of commentary published in early 2026 — including, for a time, our own — said that O. Reg. 87/25 moved fire door inspection from annual to monthly. It did not.

The monthly duty sits at Division B, Article 2.2.3.4(4), and it reads, in full:

A door in a fire separation shall be inspected monthly.

O. Reg. 87/25 does not amend Article 2.2.3.4. The requirement predates it. If a contractor or consultant tells you this is a new 2026 obligation, they have read a summary rather than the regulation.

There is no exemption from it. Article 2.2.3.4(3) does provide exceptions — for a door designed to close automatically in a fire emergency, and for a door covered by an approved fire safety plan — but read what they exempt. They apply to sentences (1) and (2), the duties to keep the door closed and check that it stays closed. They do not reach sentence (4). Every door in a fire separation is inspected monthly, without exception.

Responsibility

Who the Code holds responsible

The Fire Code places obligations on the “owner” — and defines that term more broadly than most people expect.

Division A, Article 1.4.1.2 defines an owner as:

any person, firm or corporation having control over any portion of the building or property under consideration and includes the persons in the building or property.

Article 1.2.1.1 then states that, unless otherwise specified, the owner is responsible for carrying out the provisions of the Code.

“Control over any portion” is the operative phrase. It is not limited to the registered titleholder. In practice responsibility often sits with whoever controls building maintenance, which in a managed building is the property manager rather than the owner in the abstract. In a triple-net lease it may be the tenant.

If your lease is ambiguous, resolve it now

The worst time to discover that nobody was clear on who inspects the fire doors is when a fire prevention officer asks for the records. Establish it in writing before an inspection rather than after an order lands.

Records

Undocumented compliance is unprovable compliance

Most of this industry, ourselves included until recently, states the record requirement incorrectly. Here is what the Code actually says.

The Fire Code does not require you to keep a record of the monthly fire door inspection. Article 1.1.2.1 requires records where the Code requires tests, corrective measures or operational procedures. Inspection records are mandatory only in a supported group living residence or an intensive support residence. Records of the 12-month tests at Article 2.7.2.3 are required, by Article 2.7.2.4 — but the monthly door inspection itself carries no express record duty in an ordinary commercial building.

Where records are required, Article 1.1.2.2 sets the retention: at least two years, with at least the most recent and the immediately preceding record kept at the building. Electronic records that can be produced for the Chief Fire Official on request are expressly deemed to comply. Initial verification reports for fire protection systems installed after 21 November 2007 are kept for the life of the system.

That is the law. The practical reality points the other way, and it is the reason we keep records on every visit regardless.

If a fire prevention officer asks whether your fire doors were inspected last month, an undocumented inspection is indistinguishable from one that never happened. Your approved fire safety plan may require the record in its own terms. Your insurer will ask for it after a loss. And if a door fails in a fire, nobody will be asking whether the Code compelled a record — they will be asking what you can produce.

A defensible record should show, for each door:

  • A unique identifier for the opening, so the record refers to a specific door
  • The date of inspection and who carried it out
  • What was checked and what was found
  • Photographic evidence of any deficiency
  • What corrective action was taken, and when
  • A retained history, so the pattern over time is visible

Confirm with your local fire service what they expect to see — practice varies, and your fire prevention officer will tell you directly if you ask.

Worth knowing

A US label is not automatically a Canadian one

A detail that catches people out, particularly when doors or hardware are sourced from the United States.

The Fire Code defines listed as “equipment or materials included in a list published by a certification organization accredited by the Standards Council of Canada.” That accreditation is the hook. A label from a US certification body against a US standard does not automatically satisfy it, which is why Canadian fire doors generally carry a ULC label rather than a UL one.

The practical consequence is the part that matters on site. If someone has replaced a closer, a latch, a hinge or a seal on a rated door with a part that is not listed for that assembly, the assembly is compromised — even though the door works perfectly and nothing looks wrong.

What to do

A sensible order of operations

1

Find out how many doors you have

Most buildings do not know. Walk the building and identify every opening in a fire separation and every egress door. You cannot schedule an obligation you have not counted.

2

Establish a baseline

A first full inspection tells you the condition of the stock. Expect a long deficiency list — that is normal for a building that has never been assessed.

3

Correct what must be corrected

Separate genuine code failures from wear and cosmetic issues, and deal with the first group. Most are minor and inexpensive.

4

Put the recurring schedule in place

Monthly for doors in fire separations, monthly operability checks on egress doors, and a 12-month cycle for mag locks, revolving doors and those sliding doors — with records captured for the tests. Build it into the maintenance calendar rather than reacting when an inspector arrives.

Common questions

Questions about the Code

Does monthly really mean every single fire door?
Yes. Article 2.2.3.4(4) requires that a door in a fire separation be inspected monthly, and the exceptions at 2.2.3.4(3) do not reach it — they relieve a door from being held closed, not from being inspected. Scope in a specific building is still a question for your fire prevention officer, and we would always recommend confirming with them rather than relying on any third party’s summary, including ours.
Can building staff do the monthly inspection themselves?
Legally, yes. The Fire Code does not require a licensed or certified inspector, and Ontario licenses no fire door inspectors at all — there is no provincial credential for this work. The duty sits on the owner under Article 1.2.1.1. The real question is practical rather than legal: can the person doing it recognise a failure? A door that closes and latches can still be non-compliant because of a painted-over label, a substituted part that is not listed for the assembly, or a closer that will not latch the door from a small opening angle. Many buildings use trained staff for the routine monthly inspection and an external inspector for a detailed annual assessment. Confirm the arrangement with your fire prevention officer before relying on it.
What happens if we are not compliant?
Typically a fire prevention officer issues an order with a deadline attached. The Fire Code defines an order as one made under subsection 21(1) of the Fire Protection and Prevention Act, 1997. There are also insurance implications, and in the event of a fire, liability consequences. We are not aware of any administrative monetary penalty regime applying to these provisions, and we would not rely on claims that one exists.
We have never done this. How much trouble are we in?
Most buildings we see are in the same position. Fire services generally respond well to owners who have identified the gap and are actively working through it. Having a baseline inspection and a dated remediation plan is a materially better position than having nothing.
Is NFPA 80 relevant in Ontario?
As a standard of practice, yes. As law, no — NFPA 80 does not appear anywhere in the Ontario Fire Code. Your legal obligation flows from the Fire Code and the Ontario Building Code. NFPA 80 is a US standard whose inspection criteria are widely used in Canadian practice, and we inspect against those criteria because they are thorough. But its annual frequency is a US requirement, not an Ontario one, and a contractor offering you an annual NFPA 80 inspection in Ontario is working to the wrong interval.
Where can I read the regulation myself?
O. Reg. 213/07 is published on Ontario’s e-Laws site at ontario.ca/laws/regulation/070213, and the 2026 amendment is O. Reg. 87/25. We would encourage you to read the articles that apply to your building rather than take anyone’s summary at face value. That is how the errors previously on this page came to be found.

This page is general information, not legal advice. Fire Code obligations depend on your building, its classification and its use. Your local fire prevention officer is the authority on what applies to you, and we would encourage you to speak with them directly.

Get an assessment

Not sure where your building stands?

We will walk the building, identify every opening in a fire separation and tell you what the obligation actually involves. No cost and no commitment.

If you have already received an order, say so and we will prioritise it.

647-874-2352

Monday to Friday, 8am–5pm. After-hours by arrangement.

Request service

Service Request

We reply within one business day.

Related reading

Articles on the Fire Code

Plain-language guidance on what Ontario requires and how to evidence it.

What O. Reg. 87/25 actually changed for fire doors

New egress door and electromagnetic lock duties arrived on 1 January 2026. Monthly fire door inspection was already law.

Read the article →

Fire door records: what to keep and for how long

What the Code actually requires, what it does not, and why you should keep a record either way.

Read the article →

The ten most common reasons fire doors fail inspection

What we actually find, in order of frequency — and which failures are cheap to correct.

Read the article →